Losses, cooling data and noise
The air flow direction is from bottom to top.
This table shows typical heat loss values, required air flow and noise at the nominal ratings
of the drive. The heat loss values can vary depending on voltage, cable conditions, motor
efficiency and power factor. To obtain more accurate values for given conditions, use ABB
DriveSize tool (http://new.abb.com/drives/software-tools/drivesize).
NoiseHeat dissipationAir flow
Frame size
Drive type
ACQ580-34-
Wft
3
/minm
3
/h dB(A)
U
n
= 400 V, IEC
72528012792100R11246A-4
72640012792100R11293A-4
72800012792100R11365A-4
721000012792100R11442A-4
721000012792100R11505A-4
721260012792100R11585A-4
721420012792100R11650A-4
U
n
= 480 V, IEC
72522012792100R11246A-4
72522012792100R11293A-4
72783012792100R11365A-4
72913512792100R11442A-4
72913512792100R11505A-4
72913512792100R11585A-4
721044012792100R11650A-4
U
n
= 480 V, UL (NEC)
72528012792100R11240A-4
72652512792100R11302A-4
72783012792100R11361A-4
72913512792100R11414A-4
721044012792100R11477A-4
3AXD00000586715
These losses are not calculated according to IEC 61800-9-2.
The cooling air temperature rises 30 degrees Celsius when it goes through the drive module
if the temperature of the input cooling air is 40 degrees Celsius and the drive is operating
with nominal load.
Terminal and entry data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 MCM). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening torque
50…75 N·m (37…55 lbf·ft).
172 Technical data