Power cables
The table below gives typical copper and aluminum cable types with concentric copper
shield for the drives with nominal current. The value separated by the plus sign means the
diameter of the PE conductor. See also section Terminal and entry data for the power
cables (page 172).
UL (NEC)
2)
IEC
1)
Drive type
ACQ580-34-
Cu cable typeAl cable typeCu cable type
AWG/kcmilmm
2
mm
2
U
n
= 400 V, 480 V (IEC)
2 × 2/02 × (3 × 95)2 × (3 × 70 + 35)246A-4
2 × 3/02 × (3 × 150)2 × (3 × 95 + 50)293A-4
2 × 250 MCM2 × (3 × 185)2 × (3 × 120 + 70)365A-4
2 × 400 MCM2 × (3 × 240)2 × (3 × 150 + 70)442A-4
2 × 500 MCM or 3 × 250 MCM3 × (3 × 150)3 × (3 × 95 + 50)505A-4
2 × 600 MCM or 3 × 300 MCM3 × (3 × 185)3 × (3 × 120 + 70)585A-4
2 × 700 MCM or 3 × 350 MCM3 × (3 × 240)3 × (3 × 150 + 70)650A-4
U
n
= 480 V, UL (NEC)
2 × 2/02 × (3 × 95)2 × (3 × 70 + 35)240A-4
2 × 4/02 × (3 × 150)2 × (3 × 95 + 50)302A-4
2 × 250 MCM2 × (3 × 185)2 × (3 × 120 + 70)361A-4
2 × 350 MCM2 × (3 × 240)2 × (3 × 150 + 70)414A-4
2 × 500 MCM or 3 × 250 MCM3 × (3 × 150)3 × (3 × 95 + 50)477A-4
3AXD00000586175
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2)
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible temperature of conductor
in continuous use. For North America, power cables must be rated for 75 °C (167 °F) or higher.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Terminal data for the control cables
See section Technical data (page 118).
Technical data 173

Table of Contents

Other manuals for ABB ACQ580-34

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ580-34 and is the answer not in the manual?

ABB ACQ580-34 Specifications

General IconGeneral
BrandABB
ModelACQ580-34
CategoryControl Unit
LanguageEnglish

Related product manuals