Use as motor cablingUse as input power cablingCable type
YesYes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and symmetrically constructed PE
conductor and a shield (or armor)
YesYes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and a shield (or armor), and separ-
ate PE conductor/cable
1)
1)
A separate PE conductor is required if the conductivity of the shield (or armor) is not sufficient for the PE use.
Alternate power cable types
Use as motor cablingUse as input power cablingCable type
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu, or motors
up to 30 kW (40 hp).
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu.
PVC
Note: Shielded or armored cable, or
cabling in metal conduit is always
recommended to minimize radio fre-
quency interference.
Four-conductor cabling in PVC con-
duit or jacket (three phase conduct-
ors and PE)
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu, or motors
up to 30 kW (40 hp)
Yes
EMT
Four-conductor cabling in metal
conduit (three phase conductors and
PE), eg, EMT, or four-conductor ar-
mored cable
Yes with motors up to 100 kW
(135 hp). A potential equalization
between the frames of motor and
driven equipment is required.
Yes
Shielded (Al/Cu shield or armor)
1)
four-conductor cable (three phase
conductors and a PE)
80 Guidelines for planning the electrical installation

Table of Contents

Other manuals for ABB ACQ580-34

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ580-34 and is the answer not in the manual?

ABB ACQ580-34 Specifications

General IconGeneral
BrandABB
ModelACQ580-34
CategoryControl Unit
LanguageEnglish

Related product manuals