Start-up
■ Setting the parameters
1. Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameters 15.01 Extension module type and 15.02
Detected extension module is CMOD-01.
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 is CMOD-01.
•
set the parameter 15.01 value to CMOD-01.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.
3. Set the parameters of the extension module to applicable values.
Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Reverse15.07 RO4 source
1 s15.08 RO4 ON delay
1 s15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Digital output15.22 DO1 configuration
Reverse15.23 DO1 source
1 s15.24 DO1 ON delay
1 s15.25 DO1 OFF delay
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate the
motor speed 0... 1500 rpm with a frequency range of 0...10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
1000 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
218 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O)