Parameters 237
In1+In2 Sum of sources 1 and 2. 1
In1-In2 Source 2 subtracted from source 1. 2
In1*In2 Source 1 multiplied by source 2. 3
In1/In2 Source 1 divided by source 2. 4
MIN(In1,In2) Smaller of the two sources. 5
MAX(In1,In2) Greater of the two sources. 6
AVE(In1,In2) Average of the two sources. 7
sqrt(In1) Square root of source 1. 8
sqrt(In1-In2) Square root of (source 1 - source 2). 9
sqrt(In1+In2) Square root of (source 1 + source 2). 10
sqrt(In1)+sqrt(In2) Square root of source 1 + square root of source 2. 11
40.11 Set 1 feedback filter
time
Defines the filter time constant for process feedback. 0.000 s
0.000…30.000 s Feedback filter time. 1 = 1 s
40.14 Set 1 setpoint scaling Defines, together with parameter 40.15 Set 1 output
scaling, a general scaling factor for the process PID
control chain.
The scaling can be utilized when, for example, the
process setpoint is input in Hz, and the output of the PID
controller is used as an rpm value in speed control. In this
case, this parameter might be set to 50, and parameter
40.15 to the nominal motor speed at 50 Hz.
In effect, the output of the PID controller = [40.15] when
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.
Note: The scaling is based on the ratio between 40.14
and 40.15. For example, the values 50 and 1500 would
produce the same scaling as 1 and 30.
0.00
32768.00…32767.00 Process setpoint base. 1 = 1
40.15 Set 1 output scaling See parameter 40.14 Set 1 setpoint scaling. 1500.00;
1800.00
(95.20 b0)
32768.00…32767.00 Process PID controller output base. 1 = 1
40.16 Set 1 setpoint 1
source
Selects the primary source of process PID setpoint. See
the control chain diagram on page 386.
Not selected
Not selected None. 0
Internal setpoint Internal setpoint. See parameter 40.19 Set 1 internal
setpoint sel1.
2
AI1 scaled 12.12 AI1 scaled value 3
AI2 scaled 12.22 AI2 scaled value 4
Motor potentiometer 22.80 Motor potentiometer ref act (output of the motor
potentiometer).
8
Freq in scaled 11.39 Freq in 1 scaled value 10
AI1 percent 12.101 AI1 percent value 11
No. Name/Value Description Default
FbEq 16
Operation mode
(see par. 19.01)
Scaling
Speed control 46.01 Speed scaling
Frequency control 46.02 Frequency scaling
ACS180 FW.book Page 237 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS180 and is the answer not in the manual?

ABB ACS180 Specifications

General IconGeneral
Product TypeDC Drive
Number of Phases1 or 3
IP RatingIP20
Communication InterfacesModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-40 to +70 °C
Relative Humidity5 to 95 % non-condensing
AltitudeUp to 1000 m