Parameters 105
Parameter listing
No. Name/Value Description Default
FbEq 16
01
01 Actual values
Basic signals for monitoring the drive.
All parameters in this group are read-only unless
otherwise noted.
Note: Values of these actual signals are filtered with the
filter time defined in group 46 Monitoring/scaling settings.
The selection lists for parameters in other groups mean
the raw value of the actual signal instead. For example, if
a selection is “Output frequency” it does not point to the
value of parameter 01.06 Output frequency but to the raw
value.
01.01 Motor speed used Estimated motor speed. A filter time constant for this
signal can be defined by parameter 46.11 Filter time motor
speed.
-
-30000.00… 30000.00
rpm
Estimated motor speed. See par.
46.01
01.02 Motor speed
estimated
Estimated motor speed in rpm. A filter time constant for
this signal can be defined by parameter 46.11 Filter time
motor speed.
-
-30000.00… 30000.00
rpm
Estimated motor speed. See par.
46.01
01.03 Motor speed % Actual speed in percent of the motor synchronous speed.
The filter time constant can be adjusted by parameter
46.11 Filter time motor speed.
-
-1000.00… 1000.00% Motor speed. See par.
46.01
01.04 Encoder 1 speed
filtered
Measured motor speed from Encoder 1. The filter time
constant can be adjusted by parameter 46.11 Filter time
motor speed.
-
-30000 … 30000 1=1
01.06 Output frequency Estimated drive output frequency in Hz. A filter time
constant for this signal can be defined by parameter 46.12
Filter time output frequency.
-
-500.00…500.00 Hz Estimated output frequency. See par.
46.02
01.07 Motor current Measured (absolute) motor current in A. -
0.00…30000.00 Motor current. 1=1A
01.08 Motor current % of
motor nom
Motor current (drive output current) in percent of the
nominal motor current.
-
0.0…1000.0% Motor current. 1=1%
01.09 Motor current % of
drive nom
Motor current (drive output current) in percent of the
nominal drive current.
-
0.0…1000.0% Motor current. 1=1%

Table of Contents

Other manuals for ABB ACS380 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS380 Series and is the answer not in the manual?

ABB ACS380 Series Specifications

General IconGeneral
BrandABB
ModelACS380 Series
CategoryDC Drives
LanguageEnglish

Related product manuals