Parameters 265
Fast Debug mode enabled. Cyclical data update is as fast as
possible which increases CPU load on the drive.
1
50.13 FBA A control word Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Control word sent by master to fieldbus adapter A. -
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF1 sent by master to fieldbus adapter A. -
50.15 FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF2 sent by master to fieldbus adapter A. -
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value 1 Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
50.18 FBA A actual value 2 Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT2 sent by fieldbus adapter A to master. -
51
51 FBA A settings
Fieldbus adapter A configuration.
51.01 FBA A type Displays the type of the connected fieldbus adapter
module.
0 = Module is not found or is not properly connected, or is
disabled by parameter 50.01 FBA A enable; 0 = None;
1 = PROFIBUS DP; 32 = CANopen; 37 = DeviceNet;
128 = Ethernet; 132 = PROFINET IO; 135 = EtherCAT;
136 =ETH Pwrlink; 485 = RS-485 comm;
101 =ControlNet;
This parameter is read-only.
-