266 Parameters
51.02 FBA A Par2 Parameters 51.02…51.26 are adapter module-specific.
For more information, see the documentation of the
fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
-
0…65535 Fieldbus adapter configuration parameter. 1 = 1
…… … …
51.26 FBA A Par26 See parameter 51.02 FBA A Par2.-
0…65535 Fieldbus adapter configuration parameter. 1 = 1
51.27 FBA A par refresh Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the drive
is running.
Done
Done Refreshing done. 0
Configure Refreshing. 1
51.28 FBA A par table ver Displays the parameter table revision of the fieldbus
adapter module mapping file (stored in the memory of the
drive).
In format axyz, where ax = major table revision number;
yz = minor table revision number.
This parameter is read-only.
-
Parameter table revision of adapter module. -
51.29 FBA A drive type code Displays the drive type code in the fieldbus adapter
module mapping file (stored in the memory of the drive).
This parameter is read-only.
-
0…65535 Drive type code stored in the mapping file. 1 = 1
51.30 FBA A mapping file
ver
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
This parameter is read-only.
-
0…65535 Mapping file revision. 1 = 1
51.31 D2FBA A comm status Displays the status of the fieldbus adapter module
communication.
Not
configured
Not configured Adapter is not configured. 0
Initializing Adapter is initializing. 1
Time out A timeout has occurred in the communication between the
adapter and the drive.
2
Configuration error Adapter configuration error: mapping file not found in the
file system of the drive, or mapping file upload has failed
more than three times.
3
Off-line Fieldbus communication is off-line. 4
On-line Fieldbus communication is on-line, or fieldbus adapter has
been configured not to detect a communication break. For
more information, see the documentation of the fieldbus
adapter.
5
Reset Adapter is performing a hardware reset. 6
No. Name/Value Description Default
FbEq 16

Table of Contents

Other manuals for ABB ACS380 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS380 Series and is the answer not in the manual?

ABB ACS380 Series Specifications

General IconGeneral
BrandABB
ModelACS380 Series
CategoryDC Drives
LanguageEnglish

Related product manuals