226 Parameters
36
36 Load analyzer
Peak value and amplitude logger settings.
See also section Load analyzer (page 96).
36.01 PVL signal source Selects the signal to be monitored by the peak value
logger.
The signal is filtered using the filtering time specified by
parameter 36.02 PVL filter time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.10 … 36.15.
The peak value logger can be reset using parameter
36.09 Reset loggers. The date and time of the last reset
are stored into parameters 36.16 and 36.17 respectively.
Output
power
Not selected None (peak value logger disabled). 0
Motor speed used 01.01 Motor speed used.1
Output frequency 01.06 Output frequency.3
Motor current 01.07 Motor current.4
Motor torque 01.10 Motor torque.6
DC voltage 01.11 DC voltage.7
Output power 01.14 Output power. 8
Speed ref ramp in 23.01 Speed ref ramp input.10
Speed ref ramp out 23.02 Speed ref ramp output.11
Speed ref used 24.01 Used speed reference.12
Torque ref used 26.02 Torque reference used. 13
Freq ref used 28.02 Frequency ref ramp output.14
Process PID out 40.01 Process PID output actual.16
Other Source selection (see Terms and abbreviations). -
36.02 PVL filter time Peak value logger filtering time. See parameter 36.01 PVL
signal source.
2.00 s
0.00…120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2.
The signal is sampled at 200 ms intervals.
The results are displayed by parameters
36.40 … 36.49.
Each parameter represents an amplitude range, and
shows what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 36.07 AL2 signal scaling.
Amplitude logger 2 can be reset using parameter 36.09
Reset loggers. The date and time of the last reset are
stored into parameters 36.50 and 36.51 respectively.
For the selections, see parameter 36.01 PVL signal
source.
Motor torque
See parameter 36.01 for the selections.
36.07 AL2 signal scaling Defines the monitored signal value for the amplitude
logger AL2 that corresponds to 100% sample value.
100.00
0.00…32767.00 Signal value corresponding to 100%. 1 = 1
36.09 Reset loggers Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done Reset completed or not requested (normal operation). 0
No. Name/Value Description Default
FbEq 16

Table of Contents

Other manuals for ABB ACS380 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS380 Series and is the answer not in the manual?

ABB ACS380 Series Specifications

General IconGeneral
BrandABB
ModelACS380 Series
CategoryDC Drives
LanguageEnglish

Related product manuals