112 Parameters
06.11 Main status word ABB Drives Profile Main status word. Reflects the status
of the drive irrespective of control source e.g. a fieldbus
system, control panel (keypad), PC-Tool, standard I/O,
application program or sequence programming, and
irrespective of the actual control profile which is used to
control the drive.
The bit assignments are described on page 437 (Contents
of the fieldbus control word). The state diagram (valid for
ABB drives profile) is on page 439.
This parameter is read-only.
-
0000h…FFFFh Main status word. 1 = 1
No. Name/Value Description Default
FbEq 16
Bit Name
0 Ready to switch ON
1 Ready run
2 Ready ref
3 Tripped
4 Off 2 inactive
5 Off 3 inactive
6 Switch-on inhibited
7 Warning
8 At setpoint
9 Remote
10 Above limit
11 User bit 0
12 User bit 1
13 User bit 2
14 User bit 3
15 Reserved