Parameters 167
14.79 AO1 filter time (Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Defines the filtering time constant for analog output AO1.
0.100 s
0.000…30.000 s Filter time constant. 1000 = 1 s
No. Name/Value Description Def/
FbEq16
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Unfiltered signal
Filtered signal