Parameters 297
58.04 Baud rate Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06 Communication control.
19.2 kbps
9.6 kbps 9.6 kbit/s. 2
19.2 kbps 19.2 kbit/s. 3
38.4 kbps 38.4 kbit/s. 4
57.6 kbps 57.6 kbit/s. 5
76.8 kbps 76.8 kbit/s. 6
115.2 kbps 115.2 kbit/s. 7
58.05 Parity Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit
is rebooted or the new settings validated by parameter
58.06 Communication control.
8 EVEN 1
8 NONE 1 Eight data bits, no parity bit, one stop bit. 0
8 NONE 2 Eight data bits, no parity bit, two stop bits. 1
8 EVEN 1 Eight data bits, even parity bit, one stop bit. 2
8 ODD 1 Eight data bits, odd parity bit, one stop bit. 3
58.06 Communication
control
Validates any changes in the EFB settings, or activates
silent mode.
Enabled
Enabled Normal operation. 0
Refresh settings Validates any changed EFB configuration settings. Reverts
automatically to Enabled.
1
Silent mode Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the Refresh
settings selection of this parameter.
2
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals