Functional Software description
54 DCS 500 Software Description
Field Current Con-
troller
The current controller of the field excitation unit is located inside the
field excitation unit. Some parameters are accessible via serial
communication if the current controller needs manual tuning. The
current controller is a PI-type controller that has parameters for P-
gain and I-time constant.
P-gain parameters:
F1 KP (1308)
F2 KP (1505)
Scaling: input 4095
P 1
output 4095
I-time constant parameters:
F1 KI (1309) Scale: 1 = 10 ms
F2 KI (1506) Scale: 1 = 10 ms
The maximum output voltage of the PI-controller can be limited by
means of two parameters. When the bridge is fully open the output
voltage is 0.9 * VAC. This equals the limit value 4095. The limitation
is linear so 2048 = 0.5 * 0.9 * VAC.
F1 U LIM N (1311) negative limit
F1 U LIM P (1312) positive limit
F2 U LIM N (1508) negative limit
F2 U LIM P (1509) positive limit
Field Reversal Field reversal is needed when the drive has only one armature
bridge (two-quadrant). This gives the possibility to change the speed
direction and also to regenerate the energy back to the network. The
sign of the torque reference in armature control defines the direction
of the field.
M
F1
F2
I
exc.
+
-
T
+
-
EMF
n
I
d
3 -phase
supply
G
F1
F2
+
-
T
+
-
EMF
n
I
d
I
exc.
Normal running as motor Field Reversal Braking
Figure 41 Field reversal braking principle

Table of Contents

Other manuals for ABB DCS 500B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS 500B and is the answer not in the manual?

ABB DCS 500B Specifications

General IconGeneral
BrandABB
ModelDCS 500B
CategoryMedia Converter
LanguageEnglish

Related product manuals