8.6.4 Selecting internal fault test
The internal fault may be tested by using the LHMI. When enabling the test, the
internal relay fault output contact is activated, the green Ready LED will be blinking
and internal fault test indication is shown on the LHMI. See Technical Manual for
internal relay fault output contact location.
Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words, protection
functions can operate and trip the outputs when the internal fault is
tested.
1.
Select Main Menu/Tests/IED test/Internal fault test and press .
A071156 V3 EN
Figure 75: Internal fault test
2.
Select False or True with or .
3.
Press to confirm the selection.
8.7 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.
After a composition change, an LCT indication is seen on the LHMI at the IED start-
up. At this point, PCM600 should be connected to the IED as it reads the changed
data from the IED. The LCT indication is cleared in the same way as other indications.
If PCM600 is not connected to the IED, the indication is seen again after the IED's
reboot.
Section 8 1MRS756499 A
Commissioning
100 RED615
Operation Manual

Table of Contents

Other manuals for ABB RED615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RED615 and is the answer not in the manual?

ABB RED615 Specifications

General IconGeneral
BrandABB
ModelRED615
CategoryProtection Device
LanguageEnglish

Related product manuals