Switch Country Grid Standard Display
language
Displayed
name
1 2
2 3 TURKEY HV @400V ENGLISH TURKEY HV
2 4 CEI-016 @ 400V ITALIAN CEI 016
2 5 EN50438 generic @ 400V ENGLISH EN 50438
The list of grid standards given in the table was valid at the time of issue of the manual. It will
be continually updated as new country standards with which the inverter is compatible are
introduced
If the grid standard for the country of installation is not on the list, its pre-
sence can be checked by accessing the menu “INFORMATION>Country
Selector>New Value” when the inverter is rst switched on. Then turn the
switches a05, and the grid standard for the position set will be displayed.
During this phase the inverter is on, so pay particular attention and always wear suitable pro-
tective equipment (e.g. Class 0 Category RC insulating gloves)
At the same time as the grid standard is set, the language of the dis-
play menus is also set.
The predened setting is 0 / 0 and means no grid standard is selected
and the display language is English (in this case, the “Set Country” mes-
sage will appear on the display).
If a position of switches not assigned on the display
23
is selected, “In-
valid Selection” appears.
Grid standard of the country and display language saving
The settings become xed after 24 hours of operation of the inverter (it
does not need to be connected to the grid, and only needs to be pow-
ered).
The time remaining before the settings become xed can be seen in the
dedicated menu, and a notice appears if the time has expired.
Once the settings are xed, turning the rotary switches will produce no effect. In this condi-
tion, only the language can be changed through the dedicated menu.
At any time and for any reason, the ENGLISH language of the display menu can be set by
simultaneously pressing the “ESC” and “ENTER” buttons for at least 3 seconds.
Set Country
Invalid Selection