Specifications on the behaviour of the LEDs
Next to each state of the inverter, indicated through the steady or inter-
mittent lighting of the relevant LED, a message that identies the opera-
tion it is carrying out or the detected fault/anomaly is also shown on the
display
23
, section b10, (see relevant chapter).
POWER ALARM GFI ESC UP DOWN ENTER
b23
b10
23
25
24
In the event of malfunctioning, it is extremely dangerous to try to eliminate the fault personally.
The instructions given below must be strictly followed; if you do not have the experience and
necessary qualication to work safely, please contact a specialized technician.
Insulation fault LED
What to do after an insulation fault warning
When the red LED comes on, rst try to reset the warning through the
multi-function button ESC on the LED panel
25
.
If the inverter duly reconnects to the grid, the fault was due to temporary
phenomena.
We advise having the system inspected by the installer or a specialized technician if this
malfunctioning occurs frequently.
If the inverter does not reconnect to the grid, make it safe by isolating it
(by means of the disconnect switches) on the both the DC side and the
AC side, and then contact the installer or an authorized service centre to
have the photovoltaic generator fault repaired.