- 120 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Parameter Organisation
The UMC parameters are described in groups reflecting the major function blocks of the UMC. The figures in
braces (e.g. 1.1) provide the link the menu strucutre i.e. where it is displayed.
•Motor Management lists all parameters related to motor management i.e. starting and stopping the motor
and the control function
•Protection lists all parameters related to the motor itself (e.g. nominal current) and the motor protection
functions
•Communication lists parameters related to the fieldbus communication
•IO Module lists all parameters related to the optional IO expansion modules
•Display lists all parameters directly related to the LCD panel
•Function block lists all parameters related to a specific function block.
The column "Adjustable via" shows the possible options to adjust a parameter. "All" means the parameter
can be set via UMC100-PAN, GSD-PDP22, GSD-PDQ22, EDS CANopen, EDS DeviceNet and PBDTM. Oth-
erwise the available options are listed.
Motor Management Parameters
Para-
meter
Number
Parameter Description, Explanations Options Ad-
just-
able
via
General motor management parameters
20 Control function Defines the type of starter function
Transparent (1),
Overload relay (2),
Direct starter (3),
Reverse starter (4)
Star-delta starter (5),
Pole-changing starter (7),
Actuator_1 (9),
Actuator_2 (10),
Actuator_3 (11),
Actuator_4 (12)
All
21 Rev lock-out
time
Interlocking time before a start com-
mand in the opposite direction is ac-
cepted
1-255 s All
24 YD changeover
mode
The UMC switches from star to delta
either after a defined time or if the motor
current has decreased to 90% of I
e1
Time (0),
Current (1)
All
25 YD starting
time (Time Limit
Actuator)
Time switching from star to delta. If the
changeover mode is set to 'current' this
time defines when the motor current
must be below 90% of Ie.
Defines the maximum travel time from
one end position to the opposite end
position.
1s to 360s in steps of
0,1s.
Default: 60s
Unscaled: 10 ... 3600
Example: A value of 10
means 1s
All
27 Fault output Behaviour of DO2 or DO3 in the event of
a trip or fault.
Off (0),
Flashing DO2 (1),
On DO2 (2),
Invert DO2 (3),
Flashing DO3 (4),
On DO3 (5),
Invert DO3 (6)
All