Rockwell Automation Publication 2094-UM001J-EN-P - March 2017 27
Plan the Kinetix 6000 Drive System Installation Chapter 2
Transformer Selection
The IAM module does not require an isolation transformer for three-phase
input power. However, a transformer can be required to match the voltage
requirements of the controller to the available service.
To size a transformer for the main AC power inputs, refer to the
Kinetix 6000 power specifications in the Kinetix Servo Drives Technical Data,
publication KNX-TD003
.
For example, to size a transformer to the voltage requirements of a
2094-BC01-M01-S integrated axis module:
2094-BC01-M01-S = 6 kW continuous x 1.5 = 9.0 KVA transformer
AC Line Filter Selection
These AC line filters are available for your servo drive input power.
Table 7 - Kinetix 6000 (three-phase) AC Line Filter Selection
Refer to the Kinetix Motion Accessories Specifications Technical Data,
publication KNX-TD004
, for additional AC line filter specifications.
IMPORTANT If using an autotransformer, make sure that the phase to neutral/ground
voltages do not exceed the input voltage ratings of the drive.
IMPORTANT Use a form factor of 1.5 for three-phase power (where form factor is used to
compensate for transformer, drive module, and motor losses, and to account
for utilization in the intermittent operating area of the torque speed curve).
Drive
Cat. No.
Voltage
Current
A @ 50 °C (122 °F)
Weight, approx
kg (lb)
AC Line Filter
Cat. No.
2094-AC05-MP5-S
500V AC
50/60 Hz
30 2.7 (5.9) 2090-XXLF-X330B2094-AC05-M01-S
2094-AC09-M02-S
2094-AC16-M03-S 75 5.2 (11.4) 2090-XXLF-375
2094-AC32-M05-S 100 9.5 (20.9) 2090-XXLF-3100
2094-BC01-MP5-S
500V AC
50/60 Hz
30 2.7 (5.9) 2090-XXLF-X330B2094-BC01-M01-S
2094-BC02-M02-S
2094-BC04-M03-S 75 5.2 (11.4) 2090-XXLF-375B
2094-BC07-M05-S 100 9.5 (20.9) 2090-XXLF-3100