42
71.07144.01 - EN
INSTRUCTIONS FOR FITTERS
21. PARAMETERS SETTING
To set the boiler parameters press the (– ) and (– ) buttons together for at least 6 seconds. When the function is
active, the letters “F01” will appear on the display, alternating with the value of the parameter shown.
Changing the parameters
• Press the (+/– ) buttons to scroll through the parameters;
• Press the (+/– ) buttons to change each parameter value;
• Press the button ( ) to save changes, the display shows “MEM”;
• Press the button (i) to leave the function without saving, the display shows “ESC”;
Description of parameters
Factory settings
24 F 24
F01
Type of boiler
10 = sealed chamber - 20 = atmospheric chamber
10 20
F02
Gas used
00 = NATURAL (METHANE) - 01 = LPG
00 o 01
F03 Hydraulic system
02
F04/ F05
Setting programmable relays 1 and 2 (See SERVICE instructions)
00 = no associated function
00
F06
Maximum temperature setpoint setting (°C)
00 = 76°C
(Switching off the burner at 80°C)
01 = 45°C
00
F07 Conguration DHW priority input 02
F08
Max heating power
(0-100%)
100
F09
Max DHW power
(0-100%)
100
F10
Min heating power
(0-100%)
00
F11
Waiting time in heating before a new ignition
(00-10 minutes) - 00=10 seconds
03
F12 Diagnostics (See SERVICE Instructions) --
F13
Type of exchanger
00 = 270 mm
01 = 225 mm
01 00
F14
Testing the correct position of the DHW probe
00 = Disable
01 = Enable
01 00
F15 Factory setting 01 00
F16…F18
Manufacture information --- not used
00