RM23712 TPS
13
2.8 Available Rack Mounting Kit Options
Advisory Note Available rack and cabinet mounting kits are not designed to support shipment of
the server system while installed in a rack. If you chose to do so, Chenbro advises you verify your
shipping configuration with appropriate shock and vibration testing, before shipment. Chenbro does
not perform shipping tests which cover the complex combination of unique rack offerings and
custom packaging options.
Caution: Exceeding the rail kits specified maximum weight limit or misalignment of the server in the
rack may result in failure of the rack rails, resulting in damage to the system or personal injury. Two
people or the use of a mechanical assist tool to install and align the server into the rack is highly
recommended.
Available Rack mounting kits:
84H314610-003 (Tool-less) Vale plus short rail
- 560mm max travel length
- 123 lbs. (56 Kg) max support weight
- Stab-in system install
- x8 #10-32 screws to mount rail kit on rack flange (screw kit come with rail kit
assembling) - No cable management arm support
2.9 System Level Environmental Limits
The following table defines the system level operating and non-operating environmental limits.
Table 5. System Environmental Limits Summary
Parameter
Limits
Temperature
Operating
ASHRAE Class A2 Continuous Operation. 10º C to 35º C (50º F to
95º F) with the maximum rate of change not to exceed 10°Cper hour
ASHARE Class A3 Includes operation up to 40°C for up to 900 hours
per year.
ASHARE Class A4 Includes operation up to 45°C for up to 90 hours
per year.
Shipping
-40º Cto 70º C(-40º F to 158º F)
Altitude
Operating
Support operation up to 3050m with ASHRAEclass deratings.
Humidity
Shipping
50% to 90%, non-condensing with a maximum wet bulb of 28° C (at
temperatures from 25° Cto 35° C)
Shock
Operating
Half sine, 2 g, 11 mSec
Unpackaged
Trapezoidal, 25 g, velocity change is based on packaged weight
Packaged
ISTA (International Safe Transit Association) Test Procedure 3A 2008
Vibration
Unpackaged
5 Hz to 500 Hz 2.20 g RMS random
Packaged
ISTA (International Safe Transit Association) Test Procedure 3A 2008
AC-DC
Voltage
90 V to 132 V and 180 V to 264 V
Frequency
47 Hz to 63 Hz
Source Interrup
t
No loss of data for power line drop-out of 12 mSec