ID-FLX Lite & Telecom Global Guide
115
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 12 -
Step 1
Comm object 9097 Related applications
Description
Idle time delay starts when RPM exceeds Starting RPM (page 111). Start fail is detected when during Idle
state RPM decreases below 2.
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes. IDLE/NOMINAL (PAGE 199) opens during Cooling period again.
Note: Engine can be switched between Idle and Running state by NOMINAL/IDLE (PAGE 189) in MAN
mode.
Idle time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] Starting RPM (page 111) .. MinSpeedLim (page 121) [RPM]
Default value 800 -
Step 1
Comm object 9946 Related applications
Description
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by
NOMINAL/IDLE (PAGE 189) and after Engine ShutDown.
Idle speed
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals