ID-FLX Lite & Telecom Global Guide
126
Group: Regulator
Setpoint group Load limit Related FW 2.5.0
Range [units]
OFF, CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4 [-]
Default value YES
Step -
Comm object 11842 Related applications
Description
Setpoint is determined for selection of analog input for Speed request in the controller’s MAN mode.
OFF Speed request selection is done by binary inputs. Default state.
CU: AI1-CU: AI9 Speed request via analog input of the controller only. Binary inputs are ignored.
AIO :1-AIO4
Speed request via analog input of extension module IL-NT-AIO only. Binary inputs are
ignored.
Note: Analog speed request is ignored in AUT mode.
Note: See Speed request chart (page 61).
LAI SpdRequest
6 back to List of setpoints