ID-FLX Lite & Telecom Global Guide
127
Setpoint group Load limit Related FW 2.5.0
Range [units]
CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4, RPM-BI3 [-]
Default value CU:AI1 YES
Step -
Comm object 11843 Related applications
Description
PI loop analog input selection. Source can be adjusted from controller analog inputs or from extension
module inputs. It is also possible to use Binary input 3 in function of RPM detection. The Speed request
(regulator output) is assigned to Reg Bias value in the case of selected analog input sensor fail.
Reg Input
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] 0 .. 10000 [-]
Default value 0 YES
Step 1
Comm object 11848 Related applications
Description
Constant PI regulator output when the LBI R Reg Disable = closed.
Reg Bias
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 0 YES
Step 1
Comm object 11844 Related applications
Description
Regulator requested value.
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Request 1
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals