EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #174 background imageLoading...
Page #174 background image
ID-FLX Lite & Telecom Global Guide
174
Setpoint group Sensors Spec Related FW 2.5.0
Range [units] [Always /Running /OFF]
Default value OFF -
Step -
Comm object 14283 Related applications
Description
Setting of Counter 1 and Counter 2 mode:
Always Corresponding counter counts pulses all time.
Running Corresponding counter counts pulses only when engine is running.
OFF Corresponding counter does not count pulses. Default settings.
Note: The Total 1 and Total 2 values are visible in LiteEdit Values Statistics.
The Total 1 and Total 2 values disappear from controller screen when both Counter modes 1 and 2 are
switched OFF otherwise there is new screen between existing Statistics and Alarm list.
Counter mode 1, Counter mode 2
6 back to List of setpoints
Group: AIO module
Setpoint group AIO module Related FW 2.5.0
Range [units] -100 .. 10000 [-]
Default value 0 -
Step 1
Comm object 13650 Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO1 lev1
6 back to List of setpoints
Setpoint group AIO module Related FW 2.5.0
Range [units] -100 .. 10000 [-]
Default value 0 -
Step 1
Comm object 13651 Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO2 lev1
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals