InteliLite Global Guide
450
LBI: A
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1
Description
When this input is closed, no setpoints can be adjusted from controller’s front panel and gen-set mode (OFF /
MAN / AUTO / TEST) cannot be changed.
Note: Access Lock does not protect setpoints and mode changing from LiteEdit2015. To avoid
unqualified changes the selected setpoints have to be password protected.
Also the buttons Fault Reset and Horn Reset are not blocked at all and buttons Start and Stop
in MAN mode are not blocked.
Access Lock
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
Configuration 2
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
Configuration 3
6 back to Logical binary inputs alphabetically
LBI: B
Related FW 1.2.1 Related applications AMF, MRS
Comm object 623
Description
When binary input is active and his delay Battery Charge Fail Delay (page 189) is out of time than alarm
Battery Charge Fail (page 564) is activated, written into history log and logical binary output AL BATTERY
CHARGE (PAGE 467) is activated.
Battery Charge
6 back to Logical binary inputs alphabetically