InteliLite Global Guide
599
Alarm Type Shutdown
Alarmlist message BOC Rental Timer
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs when Rental Timer BOC (page 282) elapses.
BOCRental Timer
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Short Circuit
Alarm evaluated All the time
Related applications AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
Short Circuit BOC (page 195) adjusts the short current limit
Short Circuit BOC Delay (page 195) adjusts the delay in fine steps
BOC Short Circuit
6 back to List of alarms level 2
8.2.3 Fail sensor and other types
Fls AIN Prot 601
Fls Coolant Temp 601
Fls Fuel Level 601
Fls Oil Pressure 601
For full list of Fails sensor and other types of alarms go to List of fail sensor alarms (page 600).
What Fail sensor and other types of alarms are
If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the Alarmlist. For more information see Sensor fail detection (FLS) on
page 85.