InteliLite Global Guide
103
5.4.16 Additional running engine indications
It is helpful to have information other than speed (RPM), whether the engine is rotating or not, especially if RPM
is measured from the generator frequency instead of magnetic pickup. The generator frequency measurement
can be unreliable at very low speeds and/or may have a delayed reaction to sudden and big changes (i.e. in the
moment that the engine has just started…).
The following conditions are evaluated as additional running engine indication:
Voltage on the D+ input is higher than 80% of battery voltage. Connect this input to the D+ (L) terminal of the
charging alternator and enable the D+ function by the setpoint D+ Function. If D+ terminal is not available,
leave the input unconnected and disable the function.
The pickup is not used and frequency is not detected on the pickup input. Connect the pickup input to the W
terminal of the charging alternator if you do not use pickup and the W terminal is available. If not, leave the
input unconnected.
Oil pressure > Starting Oil Pressure (page 167) setpoint. The oil pressure is evaluated from the analog input or
from the ECU if an ECU is configured.
At least one phase of generator voltage is >25% of nominal voltage.
These signals are used during start for powering down the starter motor even if still no RPM is measured and
also during stop in order to evaluate if the engine is really stopped.
5.4.17 Voltage phase sequence detection
Controller detects phase sequence voltage terminals. This protection is important after controller installation to
avoid wrong voltage phase connection. There is fix defined phase sequence in controller L1, L2, L3. When the
phases are connected in different order (e.g. L1,L3,L2 or L2,L1,L3) following alarms are detected:
Generator CCW Rotation (page 578)
5.4.18 Gen-set operation states
Engine state machine
Init Autotest during controller power on.
Not ready
Gen-set is not ready to start.
Example: When shutdown alarm is active or unit is in OFF mode.
Prestart
Prestart sequence in process, PRESTART (PAGE 506) output is closed.
Example: Usually used for preheating or processes executed prior gen-set start.
Cranking Engine is cranking, STARTER (PAGE 510) output is closed
Pause Pause between start attempts.
Starting Starting speed is reached and the Idle timer is running.
Running Gen-set is running at nominal speed.
Loaded Gen-set is running at nominal speed and GCB CLOSE/OPEN (PAGE 495) is closed.
Stop
Stop.
Example: Automatic or manual stop command was issued, engine is stopping.
Shutdown Shut-down alarm activated.

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals