InteliLite Global Guide
510
Related FW 1.2.1 Related applications AMF, MRS
Comm object 24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
Cranking Attempts (page 165) in Engine Settings group. Cranking fail pause is adjusted by setpoint Cranking
Fail Pause (page 165).
Image 8.184 Starter
The starter output opens when:
the “firing speed is reached
maximum time of cranking is exceeded
request to stop comes up
D+ value is higher than 80%
Oil pressure value is higher than Starting Oil Pressure (page 167)
Generator voltage > 25% of Nominal Voltage Ph-N (page 158) or Nominal Voltage Ph-Ph (page 159)
(any phase)
Starter
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 26
Description
Logical binary output which is still in logical 0.
Still Log 0
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 27
Description
Logical binary output which is still in logical 1.
Still Log 1
6 back to Logical binary outputs alphabetically

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals