InteliLite Global Guide
167
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0,0 .. 10,0 [bar] / Disabled
Default value 4,5 bar Alternative config NO
Step 0,1 bar
Comm object 9681 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Oil pressure limit for starting. The controller will stop cranking (STARTER (PAGE 510) goes OFF) if the oil
pressure rises above this limit.
Adjust this setpoint to Disabled to disable starting oil pressure condition.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Starting Oil Pressure
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] Enabled / ChargeFail / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9683 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Behavior of D+ terminal.
Enabled The D+ terminal is used for both functions “running engine detection and charge fail
detection.
ChargeFail The D+ terminal is used for charge fail detection only
Disabled The D+ terminal is not used.
D+ Function

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals