Alarm Type Other
Alarmlist message EM(B) - configuration mistake
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with configuration of binary input or
output of module in slot.
EM(B) - configuration mistake
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(B) - insufficient
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted in setpoint Email Address 1 (page 326) and email wasn’t
send.
EM(B) - insufficient
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(B) - missing or damaged
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in slot
(in first 5 second there was no communication and module is configured in slot).
EM(B) - missing or damaged
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Generator CCW Rotation
Alarm evaluated All the time
Related applications AMF, MRS
Description
The controller detects phase sequence on generator voltage terminals. This
protection is important after controller installation to avoid wrong voltage phase
connection. There is a fixed defined phase sequence in InteliLite controller: T35 =
N, T36 = L1, T37 = L2 and T38 = L3. When the phases are connected in a different
order, alarms are detected. This alarm prevent circuit breaker closing.
Generator CCW Rotation
6 back to List of alarms level 1