InteliLite Global Guide
452
LBI: E
Related FW 1.2.1 Related applications AMF, MRS
Comm object 164
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 193) by binary inputs. When the LBI
is activated the setpoint is decreased by 2%.
ECU Speed Down
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 165
Description
This binary input is used to set the setpoint ECU Speed Adjustment (page 193) by binary inputs. When the LBI
is activated the setpoint is increase by 2%.
ECU Speed Up
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 45
Description
This input is designed to allow the gen-set to be controlled externally, not by the controller. This feature can
be useful in case of testing the gen-set or in case of some failure, which disables the gen-set to be controlled
by the controller, but the gen-set itself is operational.
The controller behaves in the following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the gen-set control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is detected.
When the input is deactivated, the controller takes control over the gen-set according to the situation
the gen-set was in the moment of deactivation, i.e. the gen-set remains running loaded if it was
running and GCB was closed in the moment the input was deactivated.
Emergency MAN
6 back to Logical binary inputs alphabetically