InteliLite Global Guide
459
LBI: R
Related FW 1.2.1 Related applications AMF, MRS
Comm object 679
Description
When this binary input is activated, the controller sends request to inhibit regeneration of DPF (diesel
particulate filter) to ECU.
Note: ECU with Tier IV support is required for proper functionality.
Regeneration Inhib
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 620
Description
The controller is switched to the AUTO mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is closed. When opens controller is switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / TEST binary inputs
Remote control priority
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote AUTO
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 4
Description
If the input is active, the controller will not accept any actions regarding the gen-set control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote CtrlLock
6 back to Logical binary inputs alphabetically

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals