Other Control SiBE18-821_C
94 Function
5. Other Control
5.1 Demand Control
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting”.
[Demand 1 setting]
★
Other protection control functions have precedence over the above operation.
5.2 Heating Operation Prohibition Control
Heating operation is prohibited when the outdoor temperature is above 24°CDB.
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%