SiBE18-821_C Operation Mode
Function 77
1. Operation Mode
Startup control
Oil return operation
Yes
Yes
No
No
Malfunction/Standby
Normal operation
Indoor unit thermostat ON
No
Yes
Defrosting operation
Indoor unit thermostat ON
Note:
Malfunction/Standby
(R12924)
Indoor unit stop or
thermostat OFF
Operation in
stop mode
Pressure
equalization
prior to startup
Cooling or heating
operation
Oil return IN
conditions are met.
Defrost IN
conditions are met.
Operation
mode c
hange
Malfunction/
Standby
Indoor unit stop or
thermostat OFF
Indoor unit stop or
thermostat OFF
Restart standby
(Compressor stop)
Malfunction/
Standby
Pump-down
residual
operation
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
• Compressor PI control
• Electronic expansion
valve PI control
• Protection control
• Cooling startup
control
• Heating startup
control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals