Service Check Function SiBE18-821_C
334 Troubleshooting
2. Service Check Function
2.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLXS, FDXS Series
2.1.1 ARC466 Series Remote Controller
Check Method 1 1. When the timer cancel button is held down for 5 seconds, “
00
” indication appears on the
temperature display section.
2. Press the timer cancel button repeatedly until a long beep sounds.
The code indication changes in the sequence shown below.
Note: 1. A short beep “pi” and two consecutive beeps “pi pi” indicate non-corresponding codes.
2. To return to the normal mode, hold the timer cancel button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
No. Code No. Code No. Code
1 00 13 C7 25 UA
2 U4 14 A3 26 UH
3 L5 15 H8 27 P4
4 E6 16 H9 28 L3
5 H6 17 C9 29 L4
6 H0 18 C4 30 H7
7 A6 19 C5 31 U2
8 E7 20 J3 32 EA
9 U0 21 J6 33 AH
10 F3 22 E5 34 FA
11 A5 23 A1 35 H1
12 F6 24 E1 36 P9
(R11668)
< ARC466 Series >
TIMER CANCEL button

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals