Indoor Unit Control (SA Models) SiBE18-821_C
124 Function
8.4 Hot Start Control (In Heating Operation Only)
Outline At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
Detail
TH
2
: Temperature (°C) detected with the gas thermistor
TC
: High pressure equivalent saturated temperature
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Hot start control Hot start in progress
Normal operation
Normal operation
LL
OFF
Remote controller
setting
Level position
FanLouver
Hot start ending conditions
· lapse of 3 minutes
· [TH2] > 34˚C
· Tc > 52˚C
OR
(R12941)
H/L remote
controller setting
Defrost ending or oil return ending
or Thermostat ON

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals