SiBE18-821_C Indoor Unit Control (RA Models)
Function 115
7.13 Inverter POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
A
= 40 ~ 90 rpm (depending on the model)
Ex.) : POWERFUL operation in cooling mode.
7.13.1 Multi-Colored Indicator Lamp / TIMER Lamp
Features Wall Mounted Type J-Series
Current operation mode is displayed in color of the lamp of the indoor unit. Operating status can
be monitored even in automatic operation in accordance with the mode of actual operation.
The lamp color changes according to the operation.
∗
AUTO ........................................................Red / Blue
∗
DRY ..........................................................Green
∗
COOL........................................................Blue
∗
HEAT ........................................................Red
∗
FAN...........................................................White
∗
TIMER.......................................................Orange
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C
DRY Dry rotating speed +
A rpm
Lowered by 2 ~ 2.5°C
HEAT H tap + A rpm 30 ~ 32°C
FAN H tap + A rpm —
AUTO Same as cooling /
heating in POWERFUL
operation
The target temperature is
kept unchanged.
(R13571)
Target temp.
Fan
A rpm
18ËšC
POWERFUL ON
POWERFUL OFF
H tap
Set tap
20 minutes
It counts 20 min. also in the
remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
It should be the lower limit of cooling temperature.
(R11815)
Multi-colored indicator lamp /
TIMER lamp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals