Troubleshooting for Outdoor Unit SiBE18-821_C
420 Troubleshooting
Troubleshooting
Has
an indoor
unit once connected
been remove or its
address
changed?
Is
the master
controller's
connector for setting
master controller
disconnected?
Is the power
supply turned on for
indoor units displaying
malfunction?
Is the
transmission wiring
disconnected or wired
incorrectly?
Is the
transmission with
all indoor units
malfunctioning?
Is the
group No. of
malfunctioning indoor
units set?
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect the connector
correctly.
NO
Reset power supply
simultaneously for all
optional controllers for
centralized control.
YES
NO
Turn indoor unit's power
supply.
NO
YES
Fix the wiring correctly.
NO
YES
NO
YES
Fix the wiring correctly.
NO
YES
Replace the PCB of the
centralized remote
controller.
YES
(R13052)
Set the group No.
correctly.
NO
Replace the indoor unit
PCB.
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi Plus E-Series FFQ50B8V1B and is the answer not in the manual?

Daikin Super Multi Plus E-Series FFQ50B8V1B Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi Plus E-Series FFQ50B8V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals