Application Guide | iC2-Micro Frequency Converters
Selection number Selection name
0 None
1 Profile default
2 CTW valid, active low
P 5.5.1.10 Operating State at Power-up
Select operating mode for restart upon reconnection of the drive to mains voltage after power down. This function is active in Local
mode only.
Default value: 1 [Forced stop, ref = old] Parameter type: Selection
Parameter
number:
4 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Resume Restart the frequency converter, maintaining the start or stop
settings using START or STOP button, selected before power-
down of the frequency converter.
1 Forced Stop, Ref.=old Restart the frequency converter with a saved local reference after
mains voltage reappears, after pressing START.
2 Forced Stop, Ref.=0 Reset the local reference to 0 upon restarting the frequency
converter.
P 5.5.1.15 [REM/LOC] Button
Use this parameter to select the function of the REM/LOC button. To avoid accidental LOC/REM change of the drive, select [0] Disabled.
The setting can be locked by P 6.6.20 Password.
Default value: 1 [Enabled] Parameter type: Selection
Parameter
number:
46 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Disabled
1 Enabled
P 5.5.1.16 [Stop/Reset] Button
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 151