Use this parameter to select whether the drive start function is controlled via the terminals (digital input) and/or via the fieldbus. This
parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value: 3 [Logic OR] Parameter type: Selection
Parameter
number:
853 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Digital input A digital input triggers the start function.
1 Bus A serial communication port or the fieldbus triggers the start
function.
2 Logic AND The fieldbus/serial communication port and a digital input
trigger the start function.
3 Logic OR The fieldbus/serial communication port or a digital input triggers
the start function.
P 5.5.2.5 Reversing Select
Use this parameter to select whether the drive reverse function is controlled via the terminals (digital input) and/or via the fieldbus.
NOTICE
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value: 3 [Logic OR] Parameter type: Selection
Parameter
number:
854 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Digital input A digital input triggers the reversing function.
1 Bus A serial communication port or the fieldbus triggers the
reversing function.
2 Logic AND The fieldbus/serial communication port and a digital input
trigger the reversing function.
3 Logic OR The fieldbus/serial communication port or a digital input triggers
the reversing function.
P 5.5.2.6 Set-up Select