Ā© Danfoss | August 2018 AQ00000211 | 41
For more information regarding the requirements for the architecture and additional components, please see Danfoss
document, PVED-CLS Safety Manual.
P3241 indicates if a road switch is connected to the PVED-CLS. The road switch functionality will only function correct
if the following parameters are set correctly:
Parameter Description
0 = not present (EHPS)
Road switch present(connected to AD3)
255 = present.
Road switch resistance check.
255 = enabled (EHPS)
Table 10
Important
Not all combinations of these 3 parameters are valid. If an invalid condition is detected by PVED-CLS, it will enter safe
state and notify about an invalid EEPROM configuration of the Peripherals sector. See truth table in Table 11.
NO YES YES YES NO NO YES YES
Table 11
Name
Description of parameter
Range
Safety critical
parameters āSā
Cut-off valve present P3072 U8 -
Cut-off Valve Present/Not Present
Valid Values: 0 (NOT PRESENT); 255 (PRESENT)
OEM 0 255 255 S
Road switch present
(connected to AD3)
P3241 U8 -
Specifies whether the road switch is or is not present, i.e. connected to the
analogue input AD3
Valid Values: 0 (NOT PRESENT); 255 (PRESENT)
OEM 0 255 255 S