9.7.2 Carrying out an auto-detect for the CAN matrix
When a control board has been replaced or removed from the boiler, this
function must be used to detect all devices connected to the CAN bus.
1. Press the button.
2. Select Advanced Service Menu > Auto Detect.
3. Select Confirm to carry out the auto-detect.
9.7.3 Restoring the commissioning settings
This option is only available when the commissioning settings were saved
on the control panel and allows you to restore these settings.
1. Press the button.
2. Select Advanced Service Menu > Revert commissioning settings.
3. Select Confirm to restore the commissioning settings.
9.7.4 Resetting to factory settings
You can reset the boiler to the default factory settings.
1. Press the button.
2. Select Advanced Service Menu > Reset to Factory Settings.
3. Select Confirm to restore the factory settings.
9 Settings
7686707 - v.01 - 06092018 AMC 99