25INSTALLATION AND OPERATION MANUAL 25-16327-B November 2020 www.eaton.com
Section 1: System installation and design
Maintainance
Functions: See User Manual for full details.
Daily inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault
indication. Notify any faults to a system supervisior.
Weekly test
Check indicators.
Press Supervisor mode on the top left of the touch screen. Enter passcode. Select
others” tab. Press the button labeled weekly test, confirm you wish to perform the
test and the amber “System Test” LED will light. The panel will stay in the weekly
test mode for 5mins before resetting. During the weekly test, trigger a smoke
detector or call point and check the fire panel registers the device and illuminates
the correct zonal indicator. Trigger a different device every time a weekly test is
performed ensuring devices are tested in rotation until all have been checked. It is
advisable to develop a detailed a building plan highlighting devices and locations to
aid testing. The panel will reset automatically once the 5mins have elapsed. If no
devices are triggered during the weekly test the panel will abort the test and reset
after 5mins. Record weekly test in the table provided in this log book.
Quarterly
Check all previous log book entries and verify that remedial action has been taken.
Carry out the weekly test. Visually examine the batteries and their connections, by
loosening the screws behind printer door and opening the hinged front from the right
hand side.
Disconnect the mains supply and check that the battery is capable of supplying the
alarm sounders, by operating a call point.
Annual test
As Weekly Test and Quarterly Test above. Additionally test all sensors and call points
and check operation.
Every 2-3 years
Replace or return the smoke detectors for cleaning to ensure correct operation and
freedom from false alarms. Special equipment is required for cleaning
smoke detectors.
Every 5 years
Replace sealed lead acid battery.
Cleaning: When cleaning the panel, use a moist cloth. Do not use solvents or
harsh abrasives.

Table of Contents

Other manuals for Eaton CF1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton CF1200 and is the answer not in the manual?

Eaton CF1200 Specifications

General IconGeneral
BrandEaton
ModelCF1200
CategoryFire Alarms
LanguageEnglish

Related product manuals