29INSTALLATION AND OPERATION MANUAL 25-16327-B November 2020 www.eaton.com
Section 2: Commissioning
PC comissioning software
Device input programming
Fire Panel reports fire from device.
Fault Panel reports fault from device.
Reset Panel resets.
Silence Silence all currently active sounders.
Pre-alarm Panel reports pre-alarm from device.
Evacuate Panel will send all alarm
Fire/extinguisher activate Fire/extinguisher output will operate
Fre activate Fre operates
None fire Event will be logged but not displayed
(cause and effect will operate)
Test mode System in test
Isolate zones Isolate programmes zones
Isolate addresses Isolate programme addresses
Non-Latching-> device won’t latch in alarm condition, used in conjunction with
isolates.
Day / night
Devices affected :
Optical-Heat -> mode changes between heat or optoheat mode
Heat -> mode changes between Heat A1R and Heat CS

Table of Contents