2-24 L30 Line Current Differential System GE Multilin
2.5 SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
2.5SPECIFICATIONS 2.5.1 PROTECTION ELEMENTS
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
LINE CURRENT DIFFERENTIAL (87L)
Application: 2 or 3 terminal line, series compensated
line, tapped line, with charging current
compensation
Characteristic: Dual slope percent differential
Pickup current level: 0.20 to 4.00 pu in steps of 0.01
CT Tap (CT mismatch factor): 0.20 to 5.00 in steps of 0.01
Slope # 1: 1 to 50%
Slope # 2: 1 to 70%
Breakpoint between slopes: 0.0 to 20.0 pu in steps of 0.1
Level accuracy: ±3% of reading of the maximum circuit
current
DTT: Direct Transfer Trip (1 and 3 pole) to
remote L90
Operating Time: 1.0 to 1.5 power cycles duration
Asymmetrical channel delay compensation using GPS:
asymmetry up to 10 ms
In-zone transformer group compensation: 0 to 330° in steps of 30°
Inrush inhibit level: 1.0 to 40.0%f
0
in steps of 0.1
Inrush inhibit mode: per-phase, 2-out-of-3, average
Zero-sequence current differential (87LG):
87LG pickup level: 0.05 to 1.00 pu in steps of 0.01
87LG slope: 1 to 50%
87LG pickup delay: 0.00 to 5.00 s in steps of 0.01
87LG operate time: 1.5 to 2.5 cycles
PHASE/NEUTRAL/GROUND TOC
Current: Phasor or RMS
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97% to 98% of pickup
Level accuracy:
0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 × CT: ±1.5% of reading > 2.0 × CT rating
Curve shapes: IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurvesâ„¢
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier: Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type: Instantaneous/Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup: ±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
Voltage restraint: modifies pickup current for voltage in the
range of 0.1<V<0.9 VT Nominal in a
fixed linear relationship
PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 × CT rating ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operate time: <16 ms at 3 × pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz
(Neutral IOC)
Timer accuracy: ±3% of operate time or ±1/4 cycle
(whichever is greater)
NEGATIVE SEQUENCE TOC
Current: Phasor
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97% to 98% of pickup
Level accuracy: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
from 0.1 to 2.0 x CT rating
±1.5% of reading > 2.0 x CT rating
Curve shapes: IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurvesâ„¢
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
Reset type: Instantaneous/Timed (per IEEE) and Lin-
ear
Curve timing accuracy
at 1.03 to 20 x pickup: ±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
NEGATIVE SEQUENCE IOC
Current: Phasor
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Level accuracy: 0.1 to 2.0 × CT rating: ±0.5% of reading
or ±0.4% of rated (whichever is greater);
> 2.0 × CT rating: ±1.5% of reading
Overreach: <2%
Pickup delay: 0.00 to 600.00 s in steps of 0.01
Reset delay: 0.00 to 600.00 s in steps of 0.01
Operate time: <20 ms at 3 × pickup at 60 Hz
Timer accuracy: ±3% of operate time or ±1/4 cycle
(whichever is greater)