134 ADV200 • Quick start up guide
9 - Specication
9.1 Environmental Conditions
Installation location ������������������Pollution degree 2 or lower (free from direct sunligth, vi-
bration, dust, corrosive or inflammable gases, fog, vapour
oil and dripped water, avoid saline environment)
Installation altitude ������������������Max 2000m (6562 feet) above sea level (up to 1000m
without current derating).
Mechanical conditions for installation ���Vibrational stress: EN 60721-3-3 Class 3M1
Operating temperature ��������������-10…+40°C (32°…104°F)
Operating temperature (1) ������������+40 ... +50°C with derating, (+104 … +122°F with
derating)
Air humidity (operating) ��������������from 5 % to 85 % and from 1 g/m
3
to 25 g/m
3
without
moisture condensation or icing (class 3K3 as per
EN50178)
Air pressure (operating) [kPa] ���������� 86 to 106 (class 3K3 as per EN50178)
(1) In menu 4 - DRIVE CONFIG set the Ambient temperature parameter, PAR 564, to 1 (50°C).
10 % derating of output current.
The drive is suitable for use under the environmental service conditions (climate,
mechanical, pollution, etc.) dened as usual service conditions according to
EN61800-2.
9.2 Standards
Directive EC ________________________ LVD 2014/35/EU, EMC 2014/30/EU, RoHs 2011/65/EU
Climatic conditions ������������������EN 60721-3-3
Electrical safety ��������������������EN 50178, EN 61800-5-1, UL508C, UL840 degree of
pollution 2
Operating safety ��������������������(for ADV200...+SI series) IEC EN 61800-5-2 , SIL 3 ;
ISO EN 13849-1 , PL “e”
Vibration ��������������������������EN 60068-2-6, test Fc.
Shock ����������������������������EN60068-2-27
EMC compatibility �������������������EN61800-3 EN61800-3 (EMC conducted: immunity and
emissions)
Immunity: environment 2, EN12016
Conducted emission: environment 2, category C2 and C3,
EN12015
Radiated emission: determined by cabinet of final applica-
tion
Protection degree �������������������IP20, ≥ size 7: IP00
Approvals �������������������������
,