EasyManuals Logo
Home>gefran>Controller>ADV200 Series

gefran ADV200 Series User Manual

gefran ADV200 Series
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #164 background imageLoading...
Page #164 background image
164 ADV200 • Quick start up guide
10.3 External EMC lter (optional)
ADV200 series inverters (except ADV200-...-DC models) are equipped with an
internal EMI lter able to guarantee the performance levels required by EN 61800-
3 standard (according to 2nd environment, category C3) with a maximum of 20
meters of shielded motor cable (up to 50 metres for size 5 and above).
Optional external lters for different installations are listed in the table below.
Note ! The filters indicates are for connection to networks “TT” and “TN“.
In the case of supply of the inverter through IT networks, a series of special EMI filters are available.
Sizes
AC mains voltage 400V -15% … 480V +10%
Heavy duty Light duty EN 61800-3 :
Category / Environment /
Motor cable length
Type Code Type Code
1007 EMI FTF-480-7 S7GHL EMI FTF-480-7 S7GHL C2 / 1st / 30 m
1015 EMI FTF-480-7 S7GHL EMI FTF-480-7 S7GHL C2 / 1st / 30 m
1022 EMI FTF-480-7 S7GHL EMI FTF-480-7 S7GHL C2 / 1st / 30 m
1030 EMI FTF-480-7 S7GHL EMI FTF-480-16 S7GHO C2 / 1st / 30 m
1040 EMI FTF-480-16 S7GHO EMI FTF-480-16 S7GHO C2 / 1st / 30 m
2055 EMI FTF-480-16 S7GHO EMI FTF-480-16 S7GHO C2 / 1st / 30 m
2075 EMI FTF-480-16 S7GHO EMI FTF-480-30 S7GHP C2 / 1st / 30 m
2110 EMI FTF-480-30 S7GHP EMI FTF-480-30 S7GHP C2 / 1st / 30 m
3150 EMI FTF-480-30 S7GHP EMI FTF-480-42 S7GOA C2 / 1st / 30 m
3185 EMI FTF-480-42 S7GOA EMI FTF-480-55 S7GOB C2 / 1st / 30 m
3220 EMI FTF-480-55 S7GOB EMI FTF-480-75 S7GOC C2 / 1st / 30 m
4300 EMI FTF-480-75 S7GOC EMI FTF-480-75 S7GOC C2 / 1st / 30 m
4370 EMI FTF-480-75 S7GOC EMI FTF-480-100 S7GOD C2 / 1st / 30 m
4450 EMI FTF-480-100 S7GOD EMI FTF-480-130 S7GOE C2 / 1st / 30 m
5550 EMI FTF-480-130 S7GOE EMI FTF-480-180 S7GOF C3 / 2nd / 100 m
5750 EMI FTF-480-180 S7GOF EMI FTF-480-180 S7GOF C3 / 2nd / 100 m
5900 EMI FTF-480-180 S7GOF EMI-480-250 S7DGG C3 / 2nd / 100 m
61100 EMI-480-250 S7DGG EMI-480-250 S7DGG C3 / 2nd / 100 m
61320 EMI-480-250 S7DGG EMI-480-320 S7DGH C3 / 2nd / 100 m
71600 EMI-480-400 S7DGI EMI-480-400 S7DGI C3 / 2nd / 100 m
72000 EMI-480-400 S7DGI EMI-480-600 S7DGL C3 / 2nd / 100 m
72500 EMI-480-600 S7DGL EMI-480-600 S7DGL C3 / 2nd / 100 m
73150 EMI-480-600 S7DGL EMI-480-800 S7DGM C3 / 2nd / 100 m
73551 EMI-480-800 S7DGM EMI-480-800 S7DGM C3 / 2nd / 100 m
Sizes
AC mains voltage 400V -15% … 480V +10%
Heavy duty Light duty EN 61800-3 :
Category / Environment
/ Motor cable length
Type Code Type Code
400 kW
ADV-72000-KXX-4-MS 04 EMI-480-400 S7DGI EMI-480-600 S7DGL C3 / 2nd / 100 m
ADV-72000-XXX-4-SL EMI-480-400 S7DGI EMI-480-600 S7DGL C3 / 2nd / 100 m
500 kW
ADV-72500-KXX-4-MS 05 EMI-480-600 S7DGL EMI-480-600 S7DGL C3 / 2nd / 100 m
ADV-72500-XXX-4-SL EMI-480-600 S7DGL EMI-480-600 S7DGL C3 / 2nd / 100 m
630 kW
ADV-73150-KXX-4-MS 06 EMI-480-800 S7DGM EMI-480-800 S7DGM C3 / 2nd / 100 m
ADV-73150-XXX-4-SL EMI-480-800 S7DGM EMI-480-800 S7DGM C3 / 2nd / 100 m