9.6 Input electrical data
9.6.1 AC power supply
AC Input voltage, U
ln
�����������������3 ph 380 V
ac
-15% ... 500 V
ac
+5%,
AC Input frequency �������������������50/60 Hz, ± 5%
Choke �����������������������������integrated (DC) up to size 61320
Total harmonic distortion (THD) ���������40% Light duty, 50% Heavy duty (at nominal current)
Connection to TT and TN Networks �������yes, standard version
Connection to IT Networks �������������yes, special version
ADV200...-IT
only
(upon request).
Sizes
ADV200-...-4 versions (Motor cos phi 0.9 @ 400
Vac
)
AC Input current
Heavy duty (Arms) Light duty (Arms)
1007 2.1 3.7
1015 3.7 4.9
1022 4.9 6.5
1030 6.5 8.1
1040 8.1 11.1
2055 11.1 14.0
2075 14.0 19.6
2110 19.6 26.4
3150 26.4 32.3
3185 32.3 39
3220 39 53
4300 53 64
4370 64 74
4450 74 89
5550 100 143
5750 143 171
5900 171 200
61100 200 238
61320 238 285
71600 300 350
72000 350 420
72500 420 580
73150 580 640
73551 640 710
400 kW 665 800
500 kW 800 1100
630 kW 1100 1215
710 kW 1215 1350
900 kW 1650 1800
1 MW 1800 2020