54 ADV200 • Quick start up guide
5.2.6 R-SM3-ADV pre-charge card (only for sizes ≥ 71600)
Pre-charge card for drive S/N previous than S/N:34GG044151 (September 2014).
Figure 1: Terminals location
Terminals Function Voltage / Current
23 Input of the precharge enable control (15 - 35V, 5 - 11mA)
32 Output of the MLP static signal (low - active signal) (5 … 35V, 20mA source)
33 (Common) Ground of the MLP and ML static signals -
34 Reference point for Power supply +24V -
35 Power supply output +24V (32V / 300mA max)
36 Output of the ML signal (low - active signal) (5 … 35V, 20mA max sink)
37 Power supply of the ML and MLP signals (35V max)
52 (Common) Ground of the precharge enable control -
70, 72 OK Relay (max 250VAC, 1A – AC11)
Note! The jumpers shown are factory-wired.
Wiring of the OK relay contact (70 - 72) in series with the Enable chain of the ADV200 regulation card
is recommended.