48 ADV200 • Quick start up guide
5.2.5 R-PSM pre-charge card (only for sizes ≥ 71600)
Starting from ADV200 power size ≥ 160KW, the R-PSM card is used to control
the pre-charge circuit on the power supply module. When the pre-charge circuit
is connected to the mains (terminals L1 – L2 – L3), the R-PSM regulation card
generates the internal power supplies needed for operation. Therefore, additional
external power supplies are unnecessary.
If an UNDERVOLTAGE alarm is detected when the SCR bridge is enabled, the
pre-charge ramp can be repeated only after 300ms, the time needed for the phase
loss circuit to conrm that normal mains conditions have been restored.
Position of R-PSM card
Figure 5.2.5.1: Position of Switches, LEDs and Jumpers on R-PSM card
S3
S4
P1
P27
P10
D8
D9
D78
D79
D91
S1 S2 S7
LED D1...7,D80...84
TB1
S6
S5
P26
P25
P23
P28
P29
23 52 32 33 34 35 36 37 70 72
5.2.5.1 Input/Output R-PSM Regulation card
The switches and jumpers on the R-PSM card are factory-set.
If the module is used according to its standard power supply characteristics:
• ADV200-…-4 = 400VAC / 50Hz
• ADV200-…-6 = 690VAC / 50Hz
the settings should not be changed.
In case of non-standard power supply, see the conguration tables shown further
below.